Updated for 2026

Three Phase Power Calculator

Calculate balanced three-phase real power, current, voltage, apparent power, reactive power, power factor, motor input power, and horsepower with explicit line-to-line and line-to-neutral voltage handling.

Line-to-Line and Line-to-Neutral are not interchangeable.

For a balanced system, line-to-line calculations use P = √3 × VLL × I × PF. A balanced wye system using line-to-neutral voltage uses P = 3 × VLN × I × PF.

P = √3 VLL I PFP = 3 VLN I PFS² = P² + Q²PF = P/S

Balanced Three-Phase Electrical Power

Use one representative line current only for a balanced three-phase calculation.
Calculation Mode
Real Power: voltage + current + PF → kW, kVA, kvar.
Current: real power + voltage + PF → line current.
Voltage: real power + current + PF → selected RMS voltage definition.
Apparent Power: voltage + current → kVA; PF can also derive kW and kvar.
Reactive Power: voltage + current + PF → signed kvar using the selected leading/lagging convention.
Power Factor: real power ÷ apparent power derived from voltage and current.
Motor Input Power: mechanical output ÷ motor efficiency → electrical real input and estimated current.
Horsepower: convert real electrical power and mechanical horsepower units without silently applying motor efficiency.

1System Definition

Selected: Line-to-Line (VLL) — balanced power uses the √3 line-voltage relationship.

Frequency is context only; it does not appear directly in P = √3VI PF.

Balanced-system assumption: the single-voltage / single-current equations assume the phase quantities are balanced. Severe unbalance should be calculated phase-by-phase.

2Real Power Inputs

2Current Inputs

2Voltage Inputs

2Apparent Power Inputs

2Reactive Power Inputs

2Power Factor Inputs

2Motor Input Power

Efficiency ≠ Power Factor. Efficiency relates mechanical output to electrical real input; PF relates real input to apparent input.

1kW ↔ Horsepower

1 mechanical horsepower = 745.699872 W. A unit conversion does not by itself turn electrical input power into motor shaft output.

3Power Factor Type

Selected: Lagging — reactive power is reported as positive Q on this page.

All final calculations require this button click.

Calculation Results

Balanced three-phase real power
Inputs changed after the last calculation. Click “Calculate Three Phase Power” to refresh the result.
Enter your values and click “Calculate Three Phase Power” to calculate the result.

What Is Three-Phase Power?

Three-phase systems use three alternating phase quantities separated in phase. For a balanced system, total power can be calculated from a representative line voltage, line current, and power factor instead of adding three separate identical phase powers.

Line-to-Line vs Line-to-Neutral Voltage

Line-to-line voltage is measured between phase conductors. Line-to-neutral voltage is measured from a phase conductor to neutral. In a balanced wye system, VLL = √3 VLN, which is why the total-power coefficient changes from √3 to 3 depending on the voltage definition.

Real, Apparent, and Reactive Power

P = S PF    S² = P² + Q²

Real power P is measured in W, apparent power S in VA, and reactive power Q in var. These quantities should not be treated as interchangeable simply because their numerical values may be similar at high power factor.

Power Factor

Power factor magnitude is P/S. Under sinusoidal conditions it corresponds to cos φ. The page distinguishes lagging, leading, and unity assumptions for reactive-power sign while using PF magnitude for real-power magnitude.

Wye / Star Connection

For a balanced wye system, line current equals phase current and VLL = √3 VLN. Therefore P = 3 VLN I PF and P = √3 VLL I PF are equivalent when the voltage definition is used consistently.

Delta Connection

In a balanced delta connection, phase voltage equals VLL while line current and phase current have a √3 relationship. The total line-based real-power equation still uses P = √3 VLL Iline PF, so phase quantities should not be substituted without the correct connection relationships.

Balanced vs Unbalanced Three-Phase Systems

The standard √3 equation assumes balance when a single voltage, current, and PF represent all phases. For a severely unbalanced system, calculate each phase separately and sum Ptotal = PA + PB + PC using the phase voltages, currents, and power factors appropriate to the actual circuit.

Three-Phase Motor Power

If mechanical motor output is known, electrical real input can be estimated from Pin = Pout/ηmotor. Current then depends on input real power, voltage, and PF. Motor efficiency and power factor describe different relationships and must not be combined as though they are the same quantity.

kW and Horsepower

The calculator uses 1 mechanical horsepower = 745.699872 W. Converting electrical input kW to horsepower changes only the unit; it does not automatically produce shaft horsepower. A motor-efficiency relationship is required to connect electrical real input to mechanical output.

Power Triangle

The power triangle visualizes real power P, reactive power Q, and apparent power S. For the simplified sinusoidal relationship, S is the hypotenuse and S² = P² + Q². The sign of Q depends on the selected leading/lagging convention.

2026 Engineering Reference

Updated for 2026. The three-phase power equations are established electrical engineering relationships. The 2026 update refers to a review of calculator behavior, unit handling, and reference material—not a new annual three-phase power formula.

Calculation Limitations

This calculator is primarily for balanced three-phase sinusoidal power relationships. Severe unbalance, harmonics, nonsinusoidal current, power-quality studies, protection coordination, transformer vector groups, drive waveforms, and code-compliance work can require more detailed methods and equipment-specific data.

Frequently Asked Questions

1. What is three-phase power?

Three-phase power is electrical power delivered by three alternating phase conductors whose waveforms are displaced in phase. In a balanced system, the total power can be calculated from one representative line voltage, line current, and power factor. Engineers distinguish real power in watts, apparent power in volt-amperes, and reactive power in var because each describes a different part of AC power.

2. What is the three-phase power formula?

For a balanced three-phase system using line-to-line RMS voltage, real power is P = √3 × VLL × I × PF. If line-to-neutral voltage is used for a balanced wye system, the equivalent expression is P = 3 × VLN × I × PF. The voltage definition must be explicit because substituting VLL and VLN as though they are the same produces an error.

3. How do you calculate three-phase power?

Choose whether the entered voltage is line-to-line or line-to-neutral. Convert voltage and current to volts and amperes, enter a power-factor magnitude, and apply the correct balanced-system coefficient: √3 for VLL or 3 for VLN. This calculator also derives apparent power and reactive power when the input set is sufficient, while keeping leading and lagging sign conventions explicit.

4. How do I calculate three-phase kW?

Calculate real power in watts with P = √3 VLL I PF for line-to-line voltage, or P = 3 VLN I PF for line-to-neutral voltage in a balanced wye system. Divide watts by 1000 for kilowatts. The result assumes a balanced three-phase load represented by one line current and one power-factor magnitude.

5. How do I calculate three-phase amps?

Rearrange the balanced three-phase real-power equation. With line-to-line voltage, I = P/(√3 VLL PF). With line-to-neutral voltage in a balanced wye system, I = P/(3 VLN PF). Use real power in watts, voltage in volts, and power factor as a decimal. Motor current calculations may also require motor efficiency if the known power is mechanical output.

6. How do I calculate three-phase voltage?

Rearrange the same balanced power equation. For a line-to-line result, VLL = P/(√3 I PF). For a line-to-neutral result, VLN = P/(3 I PF). The result is the RMS voltage definition selected in the calculator. Do not compare a calculated VLN result directly with an equipment VLL rating without converting the voltage definition.

7. What is the difference between line voltage and phase voltage?

Line voltage usually refers to the voltage measured between two phase conductors, while phase voltage can refer to the voltage across an individual phase element. In a balanced wye system, line-to-line voltage is √3 times line-to-neutral voltage. In delta systems, phase winding voltage equals line-to-line voltage, so the relationship depends on connection and measurement points.

8. What is line-to-line voltage?

Line-to-line voltage, VLL, is the RMS voltage measured between two phase conductors. Common three-phase equipment ratings such as 400 V or 480 V are often line-to-line ratings, although equipment documentation should always be checked. When VLL and line current are used in a balanced three-phase power equation, the coefficient is √3.

9. What is line-to-neutral voltage?

Line-to-neutral voltage, VLN, is the RMS voltage from one phase conductor to the neutral point. In a balanced wye system, VLL ≈ √3 × VLN. If a calculator accepts VLN directly, total three-phase real power is P = 3 VLN I PF. This should not be confused with entering VLL into the same formula.

10. Why is √3 used in three-phase power calculations?

The √3 factor results from the 120-degree phase displacement and vector relationship between line and phase quantities in a balanced three-phase system. Using line-to-line voltage with line current gives S = √3 VLL I. The same total apparent power can be written as 3 VLN I for a balanced wye system because VLL = √3 VLN.

11. What is the difference between W and VA?

Watts measure real power actually transferred to loads, while volt-amperes measure apparent power, the RMS voltage-current product before power factor is applied. In a balanced three-phase system, S = √3 VLL I or 3 VLN I. Real power is P = S × PF, so W and VA are numerically equal only at unity power factor.

12. What is apparent power?

Apparent power S is the magnitude of complex power and is measured in VA, kVA, or MVA. For a balanced three-phase load, S = √3 VLL I when line-to-line voltage is used, or S = 3 VLN I in a balanced wye system. Apparent power combines the real and reactive components through S² = P² + Q².

13. What is reactive power?

Reactive power Q represents the AC power component associated with energy exchanged between the source and reactive electric or magnetic fields. It is measured in var, kvar, or Mvar. With apparent power S and real power P, |Q| = √(S² − P²). This calculator uses positive Q for lagging and negative Q for leading as an explicit convention.

14. What is real power?

Real power P is the average power converted to useful mechanical work, heat, light, or other net energy transfer. It is measured in W, kW, or MW. For a balanced three-phase system, P = √3 VLL I PF or, using balanced wye line-to-neutral voltage, P = 3 VLN I PF. Use measured or manufacturer values whenever the calculation supports equipment selection, loading, protection, or compliance decisions.

15. What is power factor?

Power factor is the ratio of real power to apparent power: PF = P/S. For sinusoidal balanced conditions, its magnitude also corresponds to cos φ, where φ is the phase angle between voltage and current. Power factor is dimensionless and ranges from greater than zero up to one for the magnitude calculations on this page.

16. Why does power factor affect real power?

At a fixed RMS voltage and current, apparent power S stays the same while real power equals S × PF. Therefore a lower power factor produces less real power for the same voltage-current product. In load planning, a low PF can require higher current or kVA for the same kW, which can affect conductor and equipment loading.

17. What happens when power factor is 1?

At unity power factor, PF = 1 and real power equals apparent power for the simplified sinusoidal power triangle. The phase-angle magnitude is zero and reactive power Q is zero in that model. Unity power factor does not mean an electrical system has no losses; it only describes the relationship between real and apparent power.

18. What is a lagging power factor?

A lagging power factor means current lags voltage under the chosen convention, commonly associated with inductive loads such as motors and transformers. This calculator treats lagging reactive power as positive. Sign conventions can vary among metering standards and applications, so users should confirm the convention required for a specific protection, billing, or power-flow study.

19. What is a leading power factor?

A leading power factor means current leads voltage under the chosen convention, commonly associated with capacitive behavior or overcompensation. This calculator represents leading reactive power as negative while using the positive PF magnitude for real-power calculations. Other systems may define signs differently, so the selected engineering convention should be stated with the result.

20. How do I calculate kVA in a three-phase system?

For balanced three-phase apparent power, use S = √3 VLL I with line-to-line voltage or S = 3 VLN I with balanced wye line-to-neutral voltage. Divide VA by 1000 to obtain kVA. Power factor is not required to calculate apparent power, although PF is needed if real and reactive power are also desired.

21. How do I calculate kvar?

If apparent power S and real power P are known, calculate reactive-power magnitude as |Q| = √(S² − P²). Equivalently, with PF = cos φ, Q = S sin φ. This calculator assigns positive Q for lagging and negative Q for leading. At PF = 1, Q is zero in the simplified sinusoidal power-triangle model.

22. How do I calculate three-phase motor current?

If the known motor power is electrical real input power, current follows from I = P/(√3 VLL PF) or the corresponding VLN form. If the known value is mechanical shaft output, first divide by motor efficiency to estimate electrical input power. This is why current cannot be determined from motor horsepower alone without voltage, efficiency, and power factor assumptions.

23. How do I calculate motor input power?

If mechanical motor output power Pout is known, estimated electrical input is Pin = Pout/ηmotor. Convert the mechanical output to watts first if it is entered in horsepower. Once Pin is known, estimated balanced three-phase current can be calculated using the selected voltage definition and power factor. This is an operating estimate, not a motor-sizing recommendation.

24. Is motor efficiency the same as power factor?

No. Motor efficiency compares mechanical shaft output with electrical real input power, while power factor compares real input power with apparent input power. Both affect current, but they describe different physical relationships. A motor can have high efficiency and a moderate power factor, or vice versa, depending on design and operating load.

25. How do I convert three-phase kW to horsepower?

Convert real power in kilowatts to watts and divide by 745.699872 to obtain mechanical horsepower. If the kW value represents electrical input, the converted horsepower is merely a unit conversion of electrical real power and should not automatically be labeled shaft horsepower. Mechanical output horsepower requires an efficiency relationship between electrical input and shaft output.

26. How many amps does a 10 kW three-phase motor draw?

There is no single current value for a 10 kW three-phase motor because current depends on line voltage, power factor, motor efficiency, and load. If 10 kW is mechanical output, divide by efficiency to obtain electrical real input before calculating current. Enter the actual voltage and PF rather than relying on a universal amps-per-kW shortcut.

27. How many amps does a 20 kW three-phase load draw?

A 20 kW three-phase load can draw very different currents at 208 V, 400 V, 480 V, or higher voltages, and power factor also matters. For a balanced line-to-line system, I = P/(√3 VLL PF). If 20 kW is motor shaft output instead of electrical input, motor efficiency must also be included.

28. Can I calculate three-phase power from voltage and amps?

Yes. For a balanced three-phase system, voltage and current determine apparent power, and adding power factor gives real power. With VLL, P = √3 VLL I PF; with balanced wye VLN, P = 3 VLN I PF. If power factor is unknown, voltage and current alone determine kVA but not a unique kW value.

29. Can I calculate three-phase power without power factor?

Without power factor, voltage and current can determine apparent power but not real power for a general AC load. In a balanced line-to-line system, S = √3 VLL I. Real power is P = S PF. Assuming PF = 1 without evidence can overstate real power for motors, transformers, and other inductive or capacitive loads.

30. What power factor should I use?

Use the actual power factor at the operating condition whenever possible, obtained from metering, manufacturer data, or a credible design assumption. Motor PF can vary with load, and system PF can change with capacitor banks, drives, transformers, and other equipment. Do not use one universal PF value for all three-phase loads.

31. What voltage should I enter into a three-phase calculator?

Enter the RMS voltage definition that matches your measurement or equipment data. If the rating is the voltage between phase conductors, select Line-to-Line. If you truly have phase-to-neutral voltage in a balanced wye system, select Line-to-Neutral. The calculator changes the coefficient accordingly and does not treat the two voltages as interchangeable.

32. Should I use line voltage or phase voltage?

Use line voltage when the input value is measured between two phase conductors, which is common for three-phase equipment ratings. Use phase-to-neutral voltage only when that is the quantity actually known and the balanced wye relationship applies. Selecting the wrong voltage definition introduces a factor-of-√3 error in the resulting power, current, or voltage.

33. Does frequency affect three-phase power?

Frequency is important for motors, transformers, reactance, speed, and many equipment ratings, but it does not appear directly in the basic balanced three-phase real-power equation P = √3 V I PF. This calculator records frequency as system context only. Equipment must still be operated within its rated frequency and voltage conditions.

34. Does three-phase power depend on the connection type?

The total balanced three-phase line-power equation using VLL and line current remains P = √3 VLL I PF for both common wye and delta systems. Connection type changes the relationship between line and phase voltages or currents. Problems arise when phase quantities are substituted into line formulas without applying the correct wye or delta relationships.

35. What is a wye connection?

In a wye or star connection, one end of each phase is connected to a common neutral point. For a balanced wye system, line-to-line voltage is √3 times line-to-neutral phase voltage, while line current equals phase current. This makes P = 3 VLN I PF equivalent to P = √3 VLL I PF.

36. What is a delta connection?

In a delta connection, the three phase windings or impedances form a closed triangle between the line conductors. Phase voltage equals line-to-line voltage, while line current differs from phase current by a √3 relationship in the balanced case. The line-based total-power equation remains P = √3 VLL Iline PF. Use measured or manufacturer values whenever the calculation supports equipment selection, loading, protection, or compliance decisions.

37. What is the difference between wye and delta?

Wye and delta describe different ways of connecting three phase elements. Wye provides a neutral point and has VLL = √3 VLN in the balanced case. Delta places each phase directly across line-to-line voltage and has a different line-to-phase current relationship. Both can use the same balanced line-voltage total-power equation when line quantities are used.

38. Can this calculator handle an unbalanced three-phase load?

The main calculator is designed for balanced three-phase systems represented by one voltage, one current, and one power factor. It does not reduce a severely unbalanced load to one √3 equation. For unbalanced systems, calculate each phase with its own phase voltage, current, and PF and sum the three real-power contributions.

39. How do you calculate unbalanced three-phase power?

For an unbalanced system with a known neutral reference, calculate each phase real power separately using PA = VA IA PFA, PB = VB IB PFB, and PC = VC IC PFC, then sum Ptotal = PA + PB + PC. More complex three-wire unbalanced systems may require vector or wattmeter methods and should not be forced into a balanced formula.

40. What is a three-phase power triangle?

The power triangle is a geometric representation of apparent power S, real power P, and reactive power Q for sinusoidal conditions. P is the horizontal component, Q is the vertical component, and S is the hypotenuse, so S² = P² + Q². Power factor magnitude equals P/S and corresponds to cos φ.

41. How are kW, kVA, and kvar related?

Real power P is measured in kW, apparent power S in kVA, and reactive power Q in kvar. For the simplified sinusoidal power triangle, S² = P² + Q² and PF = P/S. Knowing any two consistent power quantities often allows the third to be derived. Sign conventions for Q should be stated for leading and lagging conditions.

42. Can three-phase power be negative?

Yes, real or reactive power can be assigned negative signs depending on the adopted power-flow and metering convention, such as generation versus load or leading versus lagging reactive flow. This calculator focuses on positive real-power magnitudes for ordinary load calculations and uses an explicit sign convention for reactive power. Protection and metering studies may require different quadrant conventions.

43. What is the difference between electrical input power and motor output power?

Electrical input power is real electrical power entering the motor. Mechanical output power is shaft power delivered after motor losses. Efficiency relates them through Pout = η Pin. A direct kW-to-horsepower unit conversion does not account for motor losses, so electrical-input horsepower should not be mislabeled as mechanical shaft horsepower without an efficiency calculation.

44. Why is my three-phase power result different from another calculator?

Differences often result from line-to-line versus line-to-neutral voltage, V versus kV, A versus kA, PF entered as 0.85 versus 85, using single-phase formulas, or confusing motor shaft output with electrical input. Check whether both calculators assume a balanced system and whether their leading/lagging and horsepower conventions match. Use measured or manufacturer values whenever the calculation supports equipment selection, loading, protection, or compliance decisions.

45. Why does changing power factor change the calculated power?

For fixed voltage and current, apparent power does not change when PF changes, but real power is P = S PF. Raising PF therefore raises calculated real power at the same V and I, while lowering PF reduces it. Conversely, if real power is fixed, a lower PF requires more current or apparent power.

46. Why does changing voltage change the calculated power?

With current and power factor fixed, balanced three-phase real power is directly proportional to the selected voltage magnitude. Doubling the properly defined RMS voltage doubles P in the simplified equation. However, real equipment current, efficiency, PF, impedance, and operating point may also change with voltage, so the calculator describes the specified electrical operating point.

47. Why does changing current change the calculated power?

With voltage and power factor fixed, balanced three-phase real power is directly proportional to line current. Doubling current doubles real power in the simplified relationship. In real motors and other loads, PF and efficiency can vary with loading, so a field current change does not necessarily imply exactly proportional mechanical output.

48. Can I use this calculator for industrial motors?

Yes, for preliminary balanced three-phase electrical calculations when the correct voltage definition, current, power factor, and motor efficiency are known. Industrial motor selection and protection still require nameplate data, service factor, starting current, overload characteristics, voltage tolerance, frequency, duty cycle, code requirements, and manufacturer documentation. Use measured or manufacturer values whenever the calculation supports equipment selection, loading, protection, or compliance decisions.

49. Can I use this calculator for generators?

Yes, the real, apparent, and reactive power relationships can be used for balanced three-phase generator terminals when sign convention and operating direction are defined. Generator studies may also require voltage regulation, excitation, reactive capability, losses, efficiency, harmonics, and protection analysis that are outside this simplified calculator. Use measured or manufacturer values whenever the calculation supports equipment selection, loading, protection, or compliance decisions.

50. Can I use this calculator for transformers?

Yes for balanced terminal power relationships using the correct voltage, current, and power factor. Transformer design and loading also involve efficiency, impedance, voltage drop, temperature rise, harmonics, winding connection, kVA rating, and protection. The calculator should be treated as an electrical power cross-check rather than a transformer sizing or thermal model.

51. Can I use this calculator for electrical panels?

Yes for preliminary balanced three-phase load calculations at an electrical panel when the measured or specified voltage, current, and PF are appropriate. Panel design also requires conductor ampacity, demand factors, breaker ratings, short-circuit current, grounding, neutral loading, harmonics, code requirements, and coordination studies that are not modeled here. Use measured or manufacturer values whenever the calculation supports equipment selection, loading, protection, or compliance decisions.

52. Can I use this calculator for industrial equipment?

Yes, for balanced three-phase equipment when the voltage definition, current, and power factor are known. Drives, welders, rectifiers, UPS systems, furnaces, and other nonlinear equipment may have harmonics or nonsinusoidal waveforms where displacement PF alone is insufficient. Use equipment-specific data and appropriate power-quality methods for detailed analysis. Use measured or manufacturer values whenever the calculation supports equipment selection, loading, protection, or compliance decisions.

Related Calculators

Engineering Disclaimer

This calculator is intended for preliminary engineering and educational calculations. Results depend on the selected voltage definition, system balance, current, power factor, and motor efficiency where applicable. For equipment selection, electrical installation design, protection settings, safety-critical applications, or code compliance, verify calculations against applicable electrical standards, equipment documentation, and qualified engineering review.